HAS560 16 CHANNEL INPUT/OUTPUT BOARD, UL LISTED

Categories: ,
Share to
  • Features

• 16 channels of input/output points
• 32 I/O boards per FireNET panel (512 channels of
input/output points)
• Each channel configurable as input or output point
• Inputs are opto-isolated non-supervised pulldown
type triggered by “dry” contact from input source
• Outputs are open collector transistor pulldown
type (100mA max each) that provide “wet” voltage
output
• Simple 4 wire connection to control panel (2 for
power, 2 for data)
• All inputs/outputs can be assigned to global
functions, any event category, and used in network
wide Cause & Effect logic
• Can be mounted locally within control panel
enclosure or remotely via FN-ACC accessory
enclosure up to 4000ft from the panel
• Each I/O board has a unique address 1-32 (set via
DIP switch) on the I/O Comms Bus
• Input/Outputs are for secondary use, not for
primary fire initiation inputs or notification outputs
• Two LED’s are provided for communication status